Ag Agriculture Blog IconBehind the Scenes Blog IconConstruction Blog IconEquipment Maintenance Blog Icon Power Systems Blog Icon Thumbs Down Thumbs Up! Small Business Blog IconTachnology Blog Icon Constructioncontrol-smallcost-smallefficiency-smallflexibility-smallHoursHours Location HoursMapMapMenu AgMenu AttachmentsMenu BlogMenu CareersMenu ChecklistMenu ConstructionMenu MaintenanceMenu NewMenu PowerMenu RebuildsMenu RentMenu ServiceMenu TechnologyMenu TestimonialsMenu Training Menu Truck Menu UsedNewArtboard 1Parts Phone Phone PhonePower Systemsproductivity-smallRentalRepSafetyServiceSpecialsTechtestimonial-iconToolsTrainingTruckUsed

Caterpillar

EMCP 4.4 Master Control Panel

The EMCP 4.4 Master Control Panel is a wall mounted system that monitors and controls up to eight engine generators for operation in parallel with or without a single utility source.

Photos

Features

Specifications

  • Technical Summary
    Spec Value
    Configuration Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
    Modes of Operation Emergency standby, island, utility paralleling
    Application LV and MV (208V - 38 kV)
  • Generator Protective Devices
    Spec Value
    ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51
  • Utility Protective Devices
    Spec Value
    ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
  • Environmental Parameters
    Spec Value
    Certifications IBC, CBC, UBC & OSHPD Certified
    Control Panel Enclosure NEMA 1 wall-mounted construction
    Operating Temperature 0°C to 50°C
    Storage Temperature -20°C to +60°C
    Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
    Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Standard Equipment

Configuration

  • Wall mounted supervisory control system provides centralized monitoring and control of up to eight generators equipped with EMCP4.4 paralleling control panels

Application

  • LV and MV (208V - 15 kV) 50/60Hz

Operating Temperature

  • 0-50 C

Medium Voltage Standards

  • UL 508A

Emergency Transfer Load Manager Standard Equipment

  • Data Table Interface
  • 19" Color Touchscreen

Optional Equipment

Emergency Transfer Load Manager Optional Equipment

  • Utility Monitoring and Circuit Breaker Control I/O provided in XLM version of Master Control Panel provided in XLM version of Master Control Panel

Related Products - Attachments