Skip to main content Skip to navigation
Ag Agriculture Blog IconBehind the Scenes Blog IconConstruction Blog IconEquipment Maintenance Blog Icon Power Systems Blog Icon Thumbs Down Thumbs Up! Small Business Blog IconTachnology Blog Icon Constructioncontrol-smallcost-smallefficiency-smallflexibility-smallHoursHours Location HoursMapMapMenu AgMenu AttachmentsMenu BlogMenu CareersMenu ChecklistMenu ConstructionMenu MaintenanceMenu NewMenu PowerMenu RebuildsMenu RentMenu ServiceMenu TechnologyMenu TestimonialsMenu Training Menu Truck Menu UsedNewArtboard 1Parts Phone Phone PhonePower Systemsproductivity-smallRentalRepSafetyServiceSpecialsTechtestimonial-iconToolsTrainingTruckUsed

Caterpillar

DG275-2 (3 phase)

Frequency

60 Hz

Natural Gas Rating

275 eKW

Emissions/Fuel Strategy

U.S. EPA Certified for Non-Emergency Application

Overview

The Cat® spark-ignited generator product line for stationary applications feature permanent magnet excitation, amortisseur winding, skewed stator, voltage adjustment through the EMCP controller, Class H winding insulation and 2/3 pitch incorporated.

Photos

Features

Specifications

  • Generator Set Specifications
    Spec Value
    Frequency 60 Hz
    Natural Gas Rating 275 eKW
    Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application
    Displacement 864.71 in³
    Speed 1800 rpm
  • Engine Specifications
    Spec Value
    Fuel System Carburetor, Down Draft
    Compression Ratio 9.5:1
    Bore 5.31 in
    Stroke 6.5 in
  • Generator Set Dimensions
    Spec Value
    Length 136 in
    Width 57.6 in
    Height 66.1 in
    Weight 6274 lb

Standard Equipment

Cooling

  • Factory-installed radiator
  • 50/50 Ethylene glycol antifreeze
  • Closed coolant recovery system
  • Standard ambient temperatures up to 50°C (122°F)
  • Radiator and cooling fan complete with protective guards

Air Inlet

  • Single element air filter

Fuel

  • Primary and secondary fuel shut-off
  • Low fuel pressure switch
  • Fuel pressure test po
  • Dual lock off valves
  • NPT connection
  • Natural Gas or LP Vapor

Generator

  • Class H insulation material
  • Permanent magnet excitation
  • Full load capacity alternator
  • Permanent magnet excitation
  • Integrated Voltage Regulator
  • Class H insulation material
  • Full load capacity alternator
  • IP23 Protection
  • Matched to the performance and output characteristics of Cat engines

Exhaust

  • Exhaust outlet with 3” pipe

Controls

  • EMCP 4.2 Series generator set controller

Mounting

  • Vibration isolaton (puck type)
  • Rubber vibration isolators

Electric Starting and/or Prelube

  • Solenoid activated starter motor
  • Engine electrical system
  • Battery cables
  • Solenoid activated starter motor

Electric Power - Package Serial Number Prefix

  • Battery charging alternator

Governor

  • Electronic governor (non adjustable)

Control Panel

  • EMCP 4.2 Series generator set controller

Starting/Charging

  • Batteries with rack and cables
  • 12 volt starting motor

Optional Equipment

Starting/Charging

  • Charging alternator
  • Jacket water heater
  • Battery heater
  • Battery charger – UL Listed 10 amp

General

  • Suitable for Use as Service Equipment (SUSE)
  • CSA Certification
  • Enclosures: sound attenuated, weather protective
  • Automatic transfer switches (ATS)
  • UL 2200 package

Generator

  • Anti-condensation heater
  • Shunt trip and auxiliary contact breaker
  • Thermal magnetic or electronic trip MCCBs
  • Excitation: [ ] Permanent Magnet Excited (PM)
  • Anti-condensation heater
  • Oversize and premium generators