Skip to main content Skip to navigation
Ag Agriculture Blog IconBehind the Scenes Blog IconConstruction Blog IconEquipment Maintenance Blog Icon Power Systems Blog Icon Thumbs Down Thumbs Up! Small Business Blog IconTachnology Blog Icon Constructioncontrol-smallcost-smallefficiency-smallflexibility-smallHoursHours Location HoursMapMapMenu AgMenu AttachmentsMenu BlogMenu CareersMenu ChecklistMenu ConstructionMenu MaintenanceMenu NewMenu PowerMenu RebuildsMenu RentMenu ServiceMenu TechnologyMenu TestimonialsMenu Training Menu Truck Menu UsedNewArtboard 1Parts Phone Phone PhonePower Systemsproductivity-smallRentalRepSafetyServiceSpecialsTechtestimonial-iconToolsTrainingTruckUsed

Caterpillar

ATC-800 CONTROLLER

The ATC-900 Controller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900’s touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device’s door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-900 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

Photos

Features

Specifications

  • Technical Summary
    Spec Value
    Rating Range 120 to 600V, single phase and three phase @ 50/60 Hz
    Transfer Type Switch application dependent
    Switch Type Switch application dependent
  • ATC Controller Specifications
    Spec Value
    Input Control Voltage 120Vac (50/60 Hz) (operating range 65 to 160 Vac)
    Voltage Measurements of Utility Source 1, Source 2 and Load
    (VAB, VBC, VCA for Three Phase System)
    Voltage Measurement Range 0 to 700 Vac
    Voltage Measurement Accuracy +/-1% of full scale
    Frequency Measurements Of Source 1 and Source 2
    Frequency Measurement Range 40 Hz to 80 Hz
    Frequency Measurement Accuracy +/- 0.1 Hz
    Undervoltage Dropout Breaker Style 50 to 97% of Nominal System Voltage
    Contactor Style - 78 to 97%
    Undervoltage Pickup (Dropout +2%) to 99% of Nominal System Voltage
    Underfrequency Dropout Range 90 to 97% of Nominal System Frequency
    Underfrequency Pickup Range (Dropout +1 Hz) to 99% of Nominal System Frequency
    Overfrequency Dropout Range 103 to 110% of Nominal System Frequency
    Overfrequency Pickup Range 101% to (Dropout +1 Hz) of nominal system frequency
    Operating Temperature Range -20 to 70 degree C (-4 to +158 degree F)
    Operating Humidity Up to 90% Relative Humidity (non-condensing)
    Enclosure Compatibility
  • NEMA 12 (std mounting)
  • NEMA 3R
  • UV Resistant Faceplate
  • Ratings
    Spec Value
    System Voltage Application 120 to 600 Vac (50/60 Hz) (single or three phase)