Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Features
-
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
-
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
-
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
-
Cat ECS Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
-
Cooling System
- Designed to operate in standard ambient temperatures up to 50�C (122�F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
-
Certifications
- IBC seismic certification
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
-
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
-
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Specifications
Units for specifications
Generator Set Specifications
Standby Rating | 2750 kVA |
---|---|
Prime Power Rating | 2500 kVA |
Emissions/Fuel Strategy | Low Fuel, Low Emissions |
Voltage | 380 to 11000 volts |
Frequency | 50 Hz |
Speed | 1500 rpm |
Duty Cycle | Standby, Mission Critical, Prime, Continuous |
Maximum Rating | 2750 kVA |
Minimum Rating | 2500 kVA |
Engine Specifications
Engine Model | 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel |
---|---|
Bore | 6.69 in 170 mm |
Stroke | 8.46 in 215 mm |
Displacement | 4764.73 in 78 l |
Compression Ratio | 14.7:1 |
Aspiration | TA |
Fuel System | Electronic unit injection |
Governor Type | Adem™3 |
Generator Set Dimensions
Length - Maximum | 276.3 in 7019 mm |
---|---|
Width - Maximum | 92.1 in 2339 mm |
Height - Maximum | 118.2 in 3003 mm |
Dry Weight - Genset (maximum) | 39090 lb 17731 kg |
Standard Equipment
Air Inlet
- Air cleaner
Cooling
- Package mounted radiator
Exhaust
- Exhaust flange outlet
Fuel
- Fuel priming pump
- Secondary fuel filters
- Primary fuel filter with integral water separator
Generator
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
Power Termination
- Busbar
Control Panel
- Cat ECS 100
General
- Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment
Exhaust
- Exhaust mufflers
Generator
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
- Anti-condensation heater
- Oversize and premium generators
Power Termination
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
Control Panels
- EMCP 4.4
- Digital I/O module
- Load share module
- Generator temperature monitoring & protection
- Remote monitoring software
Mounting
- Spring type vibration isolators
- Rubber anti-vibration mounts
- IBC isolators
Starting/Charging
- Jacket water heater
- Charging alternator
- Oversize batteries
- Battery chargers
- Heavy duty starting system
- Air starting motor with control and silencer
General
- UL 2200 package
- EU Certificate of Conformance (CE)
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EEC Declaration of Conformity
- Integral & sub-base UL listed dual wall fuel tanks
- The following options are based on regional and product configuration:
- Automatic transfer switches (ATS)
- Enclosures: Sound attenuated, weather protective
- CSA Certification
- Integral & sub-base fuel tanks
Videos
-