Skip to main content Skip to navigation
Ag Agriculture Blog IconBehind the Scenes Blog IconConstruction Blog IconEquipment Maintenance Blog Icon Power Systems Blog Icon Thumbs Down Thumbs Up! Small Business Blog IconTachnology Blog Icon Constructioncontrol-smallcost-smallefficiency-smallflexibility-smallHoursHours Location HoursMapMapMenu AgMenu AttachmentsMenu BlogMenu CareersMenu ChecklistMenu ConstructionMenu MaintenanceMenu NewMenu PowerMenu RebuildsMenu RentMenu ServiceMenu TechnologyMenu TestimonialsMenu Training Menu Truck Menu UsedNewArtboard 1Parts Phone Phone PhonePower Systemsproductivity-smallRentalRepSafetyServiceSpecialsTechtestimonial-iconToolsTrainingTruckUsed

Caterpillar

G3512E Gas Generator Set

Continuous Rating

1200 ekW

Fuel Type

Natural Gas

Maximum Electrical Efficiency

42.30%

Overview

From natural gas-fueled combined heat and power (CHP) systems and emergency power for facilities, to renewable biogas energy to support the local grid, or electricity generated from coal mine gases, Caterpillar has a wide range of reliable gas power solutions.

Photos

360° View

Exterior

360� Exterior view. Double click on the image to zoom in on any area of the product.

Features

Specifications

  • Generator Set Specifications
    Spec Value
    Continuous Rating 1200 ekW
    Fuel Type Natural Gas
    Maximum Electrical Efficiency 42.30%
    Maximum Standby Rating -
    Frequency 50 Hz
    Speed 1500 rpm
  • Engine Specifications
    Spec Value
    Bore 6.7 in
    Aspiration TA
    Engine Model G3512E
    Stroke 7.5 in
    Displacement 3158 in³
  • Generator Set Dimensions
    Spec Value
    Length 181 in
    Width 65 in
    Height 89 in
    Dry Weight - Genset 27475 lb

Standard Equipment

Air Inlet

  • Two-element single-stage air cleaner with enclosure and service indicator

Control Panel

  • EMCP 4.3

Cooling

  • Jacket water and SCAC engine-driven pumps
  • Jacket water and SCAC thermostats

Exhaust

  • Dry exhaust manifolds, insulated and shielded
  • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
  • Cat-flanged face outlet on turbocharger

Fuel System

  • Engine-installed electronic control valve
  • 24V DC energized-to-run (ETR) gas shutoff valve
  • Gas pressure regulator

Fuel system

  • Electronic fuel metering valve
  • Throttle plate, 24V DC actuator, controlled by GECM
  • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve

General

  • Paint- Caterpillar Yellow except rails are gloss black
  • Parts book
  • Crankshaft vibration damper and guard
  • Operation and maintenance manuals
  • RH Service

Generator

  • SR4B
  • Permanent Magnet Excitiation
  • Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
  • Anti-condensation space heater
  • Winding temperature detectors
  • NEMA Class H insulation

Governing System

  • ADEM A4

Ignition System

  • Electronic Ignition System (controlled by GECM)
  • Individual Cylinder Detonation Sensitive Timing (DST)

Starting/Charging

  • Electric Starter

Optional Equipment

Air Inlet

  • Mounting brackets and piping
  • Air cleaner with precleaner

Circuit Breakers

  • Frame mounting
  • Right, left, rear mounted
  • 3-pole (IEC 947-2 rated)
  • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
  • S LSI, G LSIG, P LSIG-P, 4th Digit Type
  • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
  • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
  • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers

Cooling

  • Remote radiator for JW and SCAC circuits, level switch included but not wired
  • Coolant level drain line with valves, fan with guard
  • Inlet/Outlet connections

Control Panel

  • Local alarm module
  • Remote annunciator
  • Local PC monitoring
  • Remote PC monitoring
  • Engine failure relay

Exhaust

  • 305 mm (12 in.) Flange
  • 250mm-329mm Flange Expander
  • Flexible fittings

Fuel System

  • Remote mounted gas train, sized for 31.5 MJ/Nm3 (800 btu/cu ft) dry pipeline natural gas with inlet pressure range of 19.2 to 48.3 kPa (2.78 to 7 psi).

General

  • US AID emblem
  • Special paint order
  • Tool set
  • Digital diagnostic tool

Generator

  • Cable access box
  • Bearing temperature detectors
  • Generator air filter
  • European bus bars

Starting/Charging

  • 24V starting motors
  • Battery with cables and rack (shipped loose)
  • Jacket water heater
  • 45A, 24V charging alternator (requires engine driven pumps)
  • 20A, 24VDC battery charger