Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100 % rated load in one step. Our C32 generator sets are made for demands, so you can make yours.
Cat
C32 Generator Set
Overview
Photos
Videos
360° View
Exterior
360° Exterior view. Double click on the image to zoom in on any area of the product.
Showroom
C32 (50), Virtual Product Tour
Specifications
-
Generator Set Specifications
Spec Value Maximum Rating 1500 kVA Minimum Rating 910 kVA Emissions/Fuel Strategy Low Fuel, Low Emissions Voltage 400 to 3300 Volts Frequency 50 Hz Speed 1500 rpm Duty Cycle Standby, Mission Critical, Prime, Continuous -
Engine Specifications
Spec Value Engine Model C32 TA, V-12, 4-Stroke Water-Cooled Diesel Bore 5.71 in Stroke 6.38 in Displacement 1958.86 in³ Compression Ratio 15.0:1 Aspiration TA Fuel System MEUI Governor Type Adem™A4 -
Generator Set Dimensions
Spec Value Length - Minimum 164 in Length - Maximum 176.6 in Width - Minimum 66.3 in Width - Maximum 87.8 in Height - Minimum 85.1 in Height - Maximum 86.4 in Dry Weight - Genset (minimum) 14700 lb Dry Weight - Genset (maximum) 17855 lb
Standard Equipment
Air Inlet System
- Single element canister type with service indicator
Control Panel
- EMCP 4.2B
- Warning shutdowns
- Control features
- Communications
- Programmable protective relaying functions
- Digital indicators
Cooling System
- Radiator fan and fan drive
- Coolant drain line with valve
- ATAAC
- Caterpillar extended life coolant
- Fan and belt guards
- Low coolant level sensor
Exhaust
- Exhaust manifold - dry
- 203 mm (8 in) ID round flanged outlet
Fuel System
- Primary fuel filter with water separator
- Secondary fuel filters
- Fuel cooler
- Fuel priming pump
Generators and Attachments
- 6 Lead
- Salient pole
- NEMA Class H insulation
- Internal excitation (IE)
- Permanent magnet excitation (PMG)
- Reactive droop
- 3 Phase brushless
- Winding temperature detectors
- Class H temperature rise at 40C ambient
- Busbar connections, top center mounted, top cable entry
- IEC standard hole pattern
- Integrated voltage regulator (IVR)
Governing System
- ADEM(tm) A4
Mounting System
- Rubber anti-vibration mounts
- Rails - engine/generator/radiator mounting
Lube System
- Gear type lube oil pump
- Oil filter, filler and dipstick
- Integral lube Oil cooler
- Fumes disposal
- Oil drain lines and valve
- Lubricating oil
Power Termination
- Busbar
Starting / Charging System
- Battery disconnect switch
- Battery, rack and cables
- 24 Volt electric starting motor
- 45 Amp Charging alternator
General
- Caterpillar yellow with high gloss black rails & radiator
- Flywheel and flywheel housing-SAE
- SAE standard rotation
- RH service
Optional Equipment
Air Inlet System
- Heavy duty air cleaner
- Standard air cleaners
- Dual element air cleaner
Circuit breakers
- Circuit breaker wiring groups
- Enclosures - Control packaging
- Shrouds
- Power connection covers
- 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
- Center posts busbars
- Cable supports
- 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
- 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
Control Panels
- EMCP 4.3, EMCP 4.4
Cooling System
- High ambient radiator
- Extended life coolant
- Radiator duct flange
- Standard radiator
- Certified radiator
Enclosures
- Color options
- Cold weather bundle
- DC lighting package
- Sound attenuated enclosure
- Premium sound attenuated enclosure
- Enclosure fuel tank options
- Enclosure louvres - fixed and motorized
- AC Panel, outlets and lights
- Panel bracket
Exhaust System
- Flexible fittings
- Exhaust through the wall kit
- Elbow mounting kit
- Mufflers
- Flange and exhaust expanders
- Guard and shield system
- Flanges
- All C32 engines have 203 mm (8 in) exhaust outlets
Generator and Attachments
- Medium voltage generators
- Low voltage generators
Lube System
- Prelube manual sump pump
- Oil pan
- Oil level regulator
Mounting System
- IBC vibration isolators
- Spring type vibration isolators
- Mounting base types
- Standard package isolators
Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
Power Connections
- Low voltage connection cables
- Neutral grounding connection
- Center post busbars
Starting / Charging System
- Electric starting motor - Standard/heavy duty
- Jacket water heater
- 35 Amp Battery charger
- 10 Amp Battery charger
- 10 Amp enclosure Battery charger
- Standard 24 volt open package battery set - Dry
- 20 Amp Battery charger
- Space heater
Special Tests / Reports
- IBC seismic Certifications
- Custom generator TVA report
- PGS Test report @ 1.0 power factor
- Generator test report
- Standard engine test
- Standard genset Torsional Vibration Analysis (TVA) report
- CSA test and certification
- OSHPD seismic Certifications
- PGS Test report @ 0.8 power factor
General
- Special paint
- US aid emblem